Product Details:
|
Color: | Black And Orange | Packing: | Color Box |
---|---|---|---|
Weight: | Approx 830g | Power: | DC 6V Alkaline Dry Batteries LR6 1.5V×4 |
Dimension: | 275mm×145mm×40mm | Resolution: | 0.01mA |
Current Range: | 7300:0-1200A; 7300A:USD0-2000A | Product Name: | Large Caliber Three Phase Power Tester |
High Light: | VICTOR 7300 Electric Voltage Tester,7300A Electric Voltage Tester,VICTOR 7300 Tester |
Large Caliber Three Phase Electric Voltage Tester VICTOR 7300 7300A
VICTOR 7300/7300A Large Caliber Three Phase Power Tester 80mm*80mm Leakage Current With RS232 Communication Data Storage
Introduction
7300 Series Large Caliber Three Phase Power Tester is well designed and manufactured for measuring three phase AC voltage, current, leakage current, phase between current and voltage, phase between phase voltage, frequency, power energy, phase sequence, active power, reactive power, apparent power, power. It is a multifunctional, digital, intelligent tester. Its large caliber 80mm×80mm can clamp electric cable of 80mm diameter, or 96mm×4mm flat cable and steel earth wires. It has all the functions of Large Caliber Leakage Clamp Meter and Micro Power Clamp Meter. Besides, it also has this functions such as distinguish transformer wiring group, inductive and capacitive circuits, test second circuit and bus differential protection systems, read the phase relationship between CTs of the differential protection, check the meter wiring right, repair lines and equipment, etc. Provide operators with a safe, accurate and convenient tester.
7300 Series Large Caliber Three Phase Power Tester’s clamp core is made of special alloy, adopt the latest magnetic shielding techniques, can almost shield the influence from external magnetic field, to ensure the high precision, high stability and high reliability of perennial uninterrupted measurement. The meter can store 200 sets of data, with RS232 interface, upload stored data to the computer through the system software, implementing online real-time monitoring, historical inquires, dynamic display. With the function of historical data read, preserve, print, and backlight, data hold, etc. It is a necessary tool for electrical safety testing.
Model | Measurement Range | Resolution | Note |
7300 | AC0.00mA-1200A | 0.01mA | Can measure leakage current, low power |
AC 0.5W-720KW | 0.01W | ||
7300A | AC 0.0A-2000A | 0.1A | Can measure big current, high power. Can’t measure leakage current |
Function | Measure three phase AC voltage, leakage current, current, active power, reactive power, apparent power, power, phase between current and voltage, phase between phase voltage, frequency, power energy, phase sequence |
Power | 6V DC(LR6×4 alkaline dry batteries, continuously working for 12 hours) |
Test Mode | Clamp CT, integral mode |
Clamp Size | 80mm×80mm(can clamp electric cable of 80mm diameter, or 96mm×4mm flat cable and steel earth wires) |
Measured Wire Position | Measured wire at approximately the geometric center of the clamp |
Data Storage | 200 sets, “FULL” symbol indicate the memory is full |
RS232 Interface | With RS232 interface, download data to computer for analysis and management |
Communication Wire | RS232 communication wire, 1.8m |
Frequency | 50Hz ,60Hz automatic identification |
Gear Shift | Automatic shift |
Sample Rate | About 2 times/second |
Line Voltage | Below AC 600V line measurement |
Display Mode | LCD: 128dots×64dots; Display area: 43mm×29mm |
Meter Size | Length 275mm × Width 145mm × Height 40mm |
Backlight | Controlled by “ * ”key |
Data Hold | “HOLD” symbol appears |
Overflow | “OL” symbol appears |
Automatic Shutdown | Automatically shutdown about 15 minutes after power on to reduce battery consumption |
Voltage Detection | Low battery symbol “ " appears to remind the replacement of battery when the battery voltage drops below 5.2V. |
Weight | 1kg(with batteries and accessories) |
Working Current | 50mA with enabled backlight; 25mA with disabled backlight |
Working Temperature and Humidity | -10℃-40℃; 80%rh |
Storage Temperature and Humidity | -10℃-60℃; below 70%rh |
Insulation strength | AC 3700V/rms(between core and shell) |
Safety Specifications | IEC1010-1, IEC1010-2-032, 2 class of pollution, CAT Ⅲ(600V) |
VICTOR 7300 | VICTOR 7300A | |
Current Range | AC 0.00mA~1200A Resolution0.01mA | AC 0.0A~2000A Resolution0.01A |
Power Range | AC 0.5W~720KW Resolution0.01W | AC 0.0KW~1200KW Resolution0.1KW |
Line Voltage | Below AC 600V line measurement | |
Frequency Range | 25Hz~100Hz Resolution0.1Hz | |
Phase Range | 0.0°~360.0° Resolution0.1° | |
Power Factor Range | 0.3~1.0 (capacitive or inductive ) | |
Electric Energy Range | 0.0000KWh~72000KWh Resolution0.0001KWh | |
Power | 6V DC(LR6×4 alkaline dry batteries, continuously working for 12 hours) | |
Working Current | 50mA with enabled backlight; 25mA with disabled backlight | |
Weight | 1kg(with batteries and accessories) | |
Meter Size | Length 275mm × Width 145mm × Height 40mm | |
Clamp Size | 80mm×80mm(can clamp electric cable of 80mm diameter, or 96mm×4mm flat cable and steel earth wires) | |
Sample Rate | About 2 times/second | |
Frequency | 50Hz ,60Hz automatic identification | |
Communication Wire | RS232 communication. Wire: 1.8m |
Contact Person: Mrs. sales
Tel: +86 13924679853
Fax: 86-755-82268753-262